Composition introduction
Monitoring terminal, central station and user system
technical parameter
Working power supply: solar power supply, standby power supply;
Sampling rate: 10M;
Standby time: no less than 30 days in normal temperature environment;
Mean time between failures: no less than 5 years;
Number of continuous records of the terminal: 2000 times;
Transition resistance: not less than 1000 Ω;
Ranging accuracy: better than 300m;
Fault resolution: 10ms;
Fault traveling wave recording time: 10ms;
Fault frequency recording time: 100ms;
Fault diagnosis time: < 30min;
Terminal power: < 0.5W;
Communication mode: GPRS communication;
Installation distance: 30km —— 60km;
Ambient temperature: - 40 ℃ - + 80 ℃;
Relative humidity: 5% rh-100% RH;
Air pressure: 86kpa-106kpa;
Altitude: ≤ 5000m.
Technical characteristics
The principle is advanced: the Distributed installation shortens the monitoring distance, solves the problem of signal attenuation, and realizes the fault location when the high resistance is grounded;
Simple structure and convenient installation: the terminal is directly installed on the transmission line tower;
Dynamic wave speed Adaption: the system adaptively adjusts the traveling wave speed according to the fault data, and the positioning accuracy is more accurate;
High reliability and maintenance free: the terminal design takes into account the complex environmental factors, the operation does not need manual intervention, maintenance free, and the ranging terminal is standby for each other;
Complete power supply system: the terminal adopts low-power design, solar panel, super capacitor and battery redundant power supply design to improve power supply reliability;
Independent operation of the system: GPRS communication is adopted for data transmission, no interaction with other systems and no dependence on power communication dispatching system;
High speed synchronous sampling: Based on GPS timing system and precise sampling synchronization algorithm, the sampling synchronization error of the system is greatly reduced and the ranging accuracy is improved;
Powerful central station and user system: the central master station has powerful data receiving, data storage and data statistics functions. Provide detailed and complete data such as result release and fault query for the user system.